4 · TIS Tronic 260U

Room thermostat control

How the TIS Tronic 260U uses a room thermostat on I2 — pump cycling once the room is satisfied, operating and pause times, and the overheat override.

Updated

The room thermostat controls the central heating circulation pump, not the fire. When the room is cold the pump runs continuously; when the room is satisfied the controller cycles the pump instead of simply stopping it.

Controller menu row for the room thermostat setting
Thermostat menu. Source: TIS Tronic 260U manual §4.5.

Wiring requirement

The thermostat must be a dry contact on terminal I2, and its logic must be:

  • Contacts closed when the room temperature is lower than the user's setpoint → pump runs.
  • Contacts open when the room temperature is reached → pump cycles.

For a 24 VAC thermostat, use a 24 VAC SPDT relay. Wiring detail is on Room thermostat.

Inverted logic is a common fault

For correct controller operation you need a thermostat that disconnects the contacts when the room temperature is reached and connects them when it is lower. Verify with a meter.

Parameters

Why cycle instead of stop?

Cycling keeps the emitters and the distribution loop from going cold and stratifying. With a 30 s run every 1 min, water keeps moving gently, so:

  • the room temperature stays even rather than sawtoothing;
  • the boiler's return temperature does not crash, which protects it from condensation;
  • and heat continues to leave the boiler, which is important on a solid-fuel appliance you cannot simply switch off.

Set the pause to 0 only when you have another path for boiler heat — a buffer tank or a hot water load.

Overheat override

The thermostat is ignored when the boiler is hot

If the boiler temperature exceeds the maximum boiler temperature value (MBtek recommends 80 °C / 176 °F), room thermostat control is switched off to protect the boiler from overheating. The pump will run regardless of what the thermostat asks for.

This is deliberate. A wood fire cannot be turned off, so the controller must always be able to move heat out of the boiler.