Reference

Clearance reference

The UNI 60 clearance table and both clearance drawings on one printable page, plus the service-space requirements and fire safety material ratings.

Updated

One page with the clearance table, both drawings and the service-space figures — print it and take it to site.

Verify against local code

Clearance requirements for wood stoves and stove pipes vary by region. Consult local regulations or a certified building inspector. Always verify based on pipe type — single-wall or double-wall — and installation location. Keep documentation of clearance distances and code compliance for insurance and reference purposes.

Clearance for safety and service

KeyReferenceRequired distanceNotes
ABack wall to boiler24 inMinimum incline of 3°
BSide wall to boiler (right)24 inMinimum distance
CSide wall to boiler (left)24 inMinimum distance
DFront of boiler36 inRequired distance for cleaning the boiler
ECeiling to boiler28 inMinimum distance for cleaning the boiler
FCombustible to exhaust pipe12 inMinimum 6 in for double-wall stove exhaust pipe
GCombustibles to boiler12 inMinimum distance
HDistance to non-combustibles6 inMinimum distance for non-combustibles

Side elevation

Side elevation of the boiler against a masonry wall showing clearance E from the ceiling, F from the flue pipe to combustible material, G from the upper boiler body and H from the lower casing
Side view — E ceiling, F flue pipe to combustibles, G and H horizontal clearances. Source: UNI Boiler Manual, clearance addendum.

Plan view

Plan view of the boiler in a masonry room showing clearance A to the back wall, B and C to the side walls and D in front of the boiler
Plan view — A back wall, B and C side walls, D front working space. Source: UNI Boiler Manual, clearance addendum.

Service space

Section 7.2 of the boiler manual adds separate working-space figures. Where they differ from the clearance table, build to the larger.

ReferenceDistance
FrontageMinimum 4 ft
Rear wallMinimum 2 in
One side, for access to the rear of the boilerAt least 16 in

In practice: 4 ft in front and 24 in all round satisfies both sets of figures.

Fuel storage

Do not stack the fuel near the boiler at a distance of less than 4 ft.

Boiler footprint

DimensionUNI 60
Width30 in
Depth36 in
Height65 in
Weight1,224 lb
Tolerance±5 %

Total room footprint including the minimum clearances: roughly 78 in wide (30 + 24 + 24) by 96 in deep (36 + 24 back + 36 front), with 93 in of height (65 + 28).

Material fire safety ratings

ClassFlame spread indexFire resistance
Class A0–25Highest
Class B26–75Moderate
Class C76–200Lowest

The boiler's own materials:

MaterialThicknessClass rating
Mineral wool insulation1½ inClass A1
EN 10051/10 mild steel¼ inClass A*
* Subject to individual material tests. Ratings are determined by standardised tests such as ASTM E84 and E119. NextGlossary